No. |
Item |
Unit |
Requirement |
Result |
Conclusion |
1 |
Appearance and structure |
-- |
Outer dimension: ODF height: 2600mm, 2200mm and 2000mm. It is better to apply the integral multiple of 120mm for ODF width and 300mm, 450mm and 600mm for ODF depth. The tolerance of outer dimension is not more than ±2mm; The tolerance of perpendicularity of outside surface and bottom base level is not more than 3mm. |
Size: 2200×900×300mm
Size tolerance: 1mm; perpendicularity tolerance: 2mm |
Pass |
Mechanical movable part: it can turn flexibly, plug reasonably, fix securely, install and maintain easily. Door opening angle should be not less than 110 degree and gap should be not more than 3mm. |
Open type, no door |
ODF structure: the structure should be secure. The assembly should have consistency and interchangeability. The fastener is not loose. The outer parts should have comer. |
complied |
Introduced cable bending radius: When fiber optic cable is introduced into ODF, its bending radius should be not less than 15 times of cable diameter. |
20 times |
Bending radius of protective cover, gasket, fiber and pigtail: When cable/fibers pass through metal holes and turn along sharp edge, protective cover and gasket should be installed. Bending radius of fiber and pigtail should be not more than 30mm at any positions. For macro bending insensitive fiber, the bending radius should be not less than 15mm. |
Bending radius 40mm, others is complied. |
Appearance requirement: The coating surface of ODF is bright and clean, and the color is even. No sagging or grinning. No burr or corrosion for metal parts. No deformation, burr, or crack and even color for plastic parts. |
complied |
Words, diagram, symbol and mark on structure device: The words, diagram, symbol and mark on structure unit should be clear, complete and right. On fiber optic connector and splitter (if have), it should have secure and clear mark of manufacturer. |
complied |
2 |
Function requirement |
-- |
Fiber optic cable introduction, fixation and protection function: should have fiber optic cable introduction and grounding units. The unit has the following function: a)introduce and fix the cable onto the ODF, protect the cable and the fibers in the cable from being damaged; b) After the cable is stripped, the fibers has protection device and is fixed and introduced into optical fiber termination unit; c) Insulation between metal parts in fiber optic cable and ODF; d) Metal tape and strength member in fiber optic cable should be connected with high voltage protection grounding securely. |
complied |
Pass |
Fiber termination function: should have fiber termination unit. It should be convenient for fiber and pigtail splice, construction, installation and maintenance. It can fix and protect fiber optic connector from moving, and coiled fibers and pigtails from being damaged. |
complied |
Dispatch function: for common ODF, it should have vertical cabling aisle in ODF. By fiber optic connector, it is quick and convenient to dispatch fiber number and change routing sequence of fiber optic transmission system. For integrated ODF, it should have vertical cabling aisle in ODF and it should have horizontal cabling aisle between sub ODFs. By fiber optic connector, it is quick and convenient to dispatch fiber number and change routing sequence of fiber optic transmission system to realize flexible patching function between sub ODFs. |
complied |
Capacity: Every ODF capacity and unit capacity (according to the quantity of the adapters) should be stipulated in the enterprise’s standard. Fiber termination unit, fiber storage unit, and fiber distribution unit can be configured in set within full capacity. For integrated ODF, termination sub ODF, distribution sub ODF, horizontal cabling aisle and vertical cabling aisle can be configured in set within full capacity. |
ODF capacity: 60×12=720 fibers; Unit capacity: 12×12=144 fibers |
Identification and record function: It should have perfect identification and record device in ODF and unit, which is used to identify fiber number or transmission routing sequence. It is easy to modify and change the record device. |
complied |
Fiber storage function: It should have enough space for storing excess fiber in ODF and unit. |
complied |
Optical splitter installation and connection (Optional): ODF should have space for optical splitter installation and provide optical splitter connection. |
Without splitter |
3 |
Coating adhesion |
-- |
Apply metal parts with coating treatment. The coating and metal sheet should have good adhesive force. The adhesive force should be not lower than Level 2 in Table 1 of GB/T9286-1998. |
Complied with Level 0 |
Pass |
4 |
Voltage resistance level (normal) |
-- |
Between high voltage protection grounding unit and ODF ≥3000V (DC) 1min, no puncture, no arc-over. |
no puncture, no arc-over |
Pass |
5 |
Insulation resistance |
MΩ |
Between high voltage protection grounding unit and ODF ≥1000MΩ/500V (DC) |
7.1×106 |
Pass |
6 |
Combustion testing |
s |
Comply with one of the following conditions:
a)The sample is not on fire.
Removed away from the fire, the sample will inflame with flame not more than 10s and the flame or the flaming particles dropping from the sample will not burn the bottom layer under the sample. |
<1 |
Pass |
10 |
High temperature testing |
Appearance |
-- |
The coating surface of ODF is bright and clean, and the color is even. No sagging or grinning. No burr or corrosion for metal parts. No deformation, burr, or crack and even color for plastic parts. |
complied |
Pass |
8 |
Voltage resistance level |
-- |
Between high voltage protection grounding unit and ODF ≥3000V (DC) 1min, no puncture, no arc-over. |
no puncture, no arc-over |
Pass |
9 |
Insulation resistance |
MΩ |
Between high voltage protection grounding unit and ODF ≥1000MΩ/500V (DC) |
6.5×106 |
Pass |
10 |
Low temperature testing |
Appearance |
-- |
The coating surface of ODF is bright and clean, and the color is even. No sagging or grinning. No burr or corrosion for metal parts. No deformation, burr, or crack and even color for plastic parts. |
complied |
Pass |
11 |
Voltage resistance level |
-- |
Between high voltage protection grounding unit and ODF ≥3000V (DC) 1min, no puncture, no arc-over. |
no puncture, no arc-over |
Pass |
12 |
Insulation resistance |
MΩ |
Between high voltage protection grounding unit and ODF ≥1000MΩ/500V (DC) |
6.1×106 |
Pass |
13 |
Damp and hot testing |
Appearance |
-- |
The coating surface of ODF is bright and clean, and the color is even. No sagging or grinning. No burr or corrosion for metal parts. No deformation, burr, or crack and even color for plastic parts. |
complied |
Pass |
14 |
Voltage resistance level |
-- |
Between high voltage protection grounding unit and ODF ≥3000V (DC) 1min, no puncture, no arc-over. |
no puncture, no arc-over |
Pass |
15 |
Insulation resistance |
MΩ |
Between high voltage protection grounding unit and ODF ≥1000MΩ/500V (DC) |
6.7×106 |
Pass |
16 |
Salt spraying testing |
Appearance |
-- |
The coating surface of ODF is bright and clean, and the color is even. No sagging or grinning. No burr or corrosion for metal parts. No deformation, burr, or crack and even color for plastic parts. No visual rust. |
complied |
Pass |